Switchgear Testing / Switchgear FAT Test 

The switchgear testing (FAT Test) is performed after successful completion of assembly inspection. You may also review the switchgear step by step assembly inspection and testing instruction.

2 Free CPD Hours Courses - Completely Free

Enroll, Watch the Video, Take the Test, Download Your Cert and Submit to the API . 2 free courses are availble each with 2 hours credit. (Total 4 hours) - 1) ASME V Articl II , 2) ASME V Article 6 & 7 

Mechanical Operation Test

Switchgear testing

The mechanical operations of draw-out mechanism, switching mechanism, shutter mechanism, earthing facility mechanism and the mechanical interlocks shall be verified to be normal. The unit of the same size with draw-out mechanism shall have interchangeability.

Sequence Test

The electrical sequential operation of devices shall be tested to ensure that the electrical systems within the switchgear and MCC are of proper structure and connected per the approved schematic diagram and that they work normally.

Electrical Operation Test

Electrical operation test for equipment installed in switchgear and MCC (circuit breakers, magnetic contactors, switches, and relays, etc.), shall be carried out together by providing the combination of simulated input and the output circuit, and it shall be verified that the operation is normal, as per IEC 60439, 8.3.1.

Insulation Resistance Test

The insulation resistance shall be measured before and after voltage withstand test.  The measuring shall be carried out by 500 V insulation resistance tester (or as specified in the approved procedure), and the measuring places and allowable insulation resistance value for each group of MCC shall be as follows or specified values:

For the testing earthed circuit, the connection to the earth shall be removed before the test.

Voltage Withstand Test @ Switchgear Testing

After the insulation resistance test, voltage withstand tests for main circuit and control circuit shall be carried out, and no electrical or mechanical defects shall be found. The specified commercial frequency test voltage shall be applied between live parts and earth for specified duration.

For the testing earthed circuit, the connection to the earth, shall be removed prior to the test.  Furthermore, when electronic equipment for control or signal and electronic instrument or DC control equipment are included in the control circuit, they shall be disconnected or removed during the test.